Error Code 104

Troubleshooting guide for the Carrier Outdoor Packaged Units system fault 104.

Disclaimer: This information is for general reference. Error codes can vary by model and production year. Always refer to your machine's specific manual and the information printed on the unit itself.

System Diagnosis

Current Sensor Failure - Compressor C1. Current sensor output is stuck high, usually due to wiring error or loose connection.

Potential Causes & Solutions

  • Check compressor C1 current sensor wiring, connector, and mounting.
  • Verify current sensor is correctly clamped on compressor wire.
  • Measure sensor output.
  • Replace current sensor if output is stuck high.

Verify Before Replacing Parts

  1. Confirm the exact Carrier model family and outdoor packaged units context before acting on a generic code description.
  2. Verify the sensor or thermistor reading against the expected range for the current operating condition.
  3. Check the sensor harness and board connection before condemning the sensor itself.
  4. After the correction, run the system long enough to confirm the code does not return under normal load.

Field Signals to Confirm

What usually confirms it

Sensor values that do not match the operating condition or drift when the harness is moved.

What can fool you

A control board issue can look like a failed sensor if the reference voltage or connector is unstable.

When to Escalate the Call

  • Sensor values remain unstable after connector and board checks.
  • The model uses a proprietary sensor curve you cannot verify confidently in the field.

Diagnose with Confidence

Use the ACLogics AI assistant to walk through this error code step-by-step.

Included in Diagnosis Workflow

1

Ask

Upload nameplate & symptoms

2

Diagnose

AI isolates the likely outdoor packaged units branch behind code 104

3

Report

Document the verified result and next action

Related Carrier Outdoor Packaged Units Codes