Standby
Standby. No command for unit operation.
Low Pressure Control Open
Low Pressure Control Open. The ICC detects the LPC is open. Note: The low pressure control is ignored for the first 90 seconds of compressor operation.
Low Line Voltage or No Line Voltage Fault
Low Line Voltage or No Line Voltage Fault.
High Line Voltage Fault
High Line Voltage Fault.
High Pressure Control Open
High Pressure Control Open. The ICC detects the HPC is open.
Fuse Open
Fuse Open. The ICC detects the on-board fuse is open.
Low Air Flow
Low Air Flow. The ICC detects that the indoor unit is not providing the minimum airflow requirements.
Condenser Coil Temperature Fault
Condenser Coil Temperature Fault. The sensor detects an abnormally low or high coil temperature.
Outdoor Ambient Temperature Fault
Outdoor Ambient Temperature Fault. The sensor detects an abnormally low or high outdoor ambient temperature.
Internal Control Fault
Internal Control Fault. The sensor detects an abnormally low or high outdoor ambient temperature. The control is not functioning properly.
First Stage Cooling
First Stage Cooling. Unit has received a command for first stage cooling.
Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
Second Stage Cooling
Second Stage Cooling. Unit has received a command for second stage cooling.
First Stage Heat Pump
First Stage Heat Pump. Unit has received a command for first stage heat pump.
Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active
Anti-short cycle timer (3 minutes) or Minimum run timer (30 seconds) active.
Second Stage Heat Pump
Second Stage Heat Pump. Unit has received a command for second stage heat pump.
Defrost Active
Defrost Active. The unit is undergoing a defrost cycle.
Test Mode
Test Mode.
Protector Trip
Protector Trip. A command for compressor operation is present but no current is measured to the compressor.
Long Run Time (Compressor)
Long Run Time (Compressor). The compressor has continuously run for more than 18 hours in the cooling mode.
High Pressure
High Pressure. Compressor limit has opened four (4) times within a call for operation.
Short Cycling
Short Cycling. ICC detects the run time for the past four (4) compressor or cycles is less than three (3) minutes each.
Locked Rotor
Locked Rotor. The ICC detects four (4) consecutive protector trips have occurred and the average run time for each trip is less than 15 seconds.
Open circuit (Compressor Will not Run)
Open circuit (Compressor Will not Run). The ICC has had a protector trip for longer than 4 hours.
Compressor Open Start Circuit
Compressor Open Start Circuit. The ICC detects current in the Run circuit but not in the Start circuit of the compressor.
Compressor Open Start Circuit
Compressor Open Start Circuit. The ICC detects current in the Run circuit but not in the Start circuit of the compressor four (4) times in one compressor call.
Compressor Open Run Circuit
Compressor Open Run Circuit. The ICC detects current in the Start circuit but not in the Run circuit of the compressor.
Compressor Open Run Circuit
Compressor Open Run Circuit. The ICC detects current in the Start circuit but not in the Run circuit of the compressor four (4) times in one compressor call.
Low Secondary Volts
Low Secondary Volts. The secondary voltage at R and C is below 18VAC.
Active Protection, Low Pressure Control Trip
Active Protection, Low Pressure Control Trip.
Active Protection, High Pressure Control Trip
Active Protection, High Pressure Control Trip.
No Shared Data
No Shared Data.
Airflow CFM Mismatch
Airflow CFM Mismatch. The indoor air mover (air handler/furnace) cannot supply the required airflow for proper system operation.
Memory Card Invalid
Memory Card Invalid. The data in the memory card inserted into the control board does not match the data in the control.
Old Shared Data
Old Shared Data. System data is obsolete.