Carrier Outdoor Packaged Units

Error Code 93

Troubleshooting guide for the Carrier Outdoor Packaged Units system fault 93.

Disclaimer: This information is for general reference. Error codes can vary by model and production year. Always refer to your machine's specific manual and the information printed on the unit itself.

System Diagnosis

Suction Pressure Transducer Failure - Circuit B. Suction pressure is outside the valid range and the circuit cannot run while active.

Potential Causes & Solutions

  • Check circuit B suction pressure transducer wiring and 5V supply.
  • Measure transducer output voltage.
  • Inspect for refrigerant system issues causing out-of-range pressure.
  • Replace transducer if signal is incorrect.

Verify Before Replacing Parts

  1. Confirm the exact Carrier model family and outdoor packaged units context before acting on a generic code description.
  2. Verify airflow first, then confirm operating pressures and temperature relationship before adjusting charge.
  3. Look for restrictions, iced coils, or dirty heat-transfer surfaces that can mimic a charge problem.
  4. After the correction, run the system long enough to confirm the code does not return under normal load.

Field Signals to Confirm

What usually confirms it

Pressure and temperature readings that stay out of range after airflow is verified.

What can fool you

Dirty coils or airflow restrictions can look like a charge problem until the air side is cleaned up.

When to Escalate the Call

  • You suspect a restriction, leak, or compressor issue that needs deeper system evaluation.
  • The readings do not normalize after airflow and coil conditions are corrected.