Lennox Equipment not specified

Lennox Error Code 250

Equipment not specified:

What It Means

  • GF Primary Limit Switch Open

Causes & actions from Lennox

How it shows
  • iComfort S30 alert: 250

Priority condition: Service Soon The furnace primary limit switch is open. If limit switch is not closed within three minutes, the unit will go into a 60 minute soft lockout (Watchguard mode). Perform the following: • Check for high gas pressure. • Check for low supply air. Low supply air due to being plugged or restriction in system (example: dirty air filter or blockage in duct work). • Check for proper firing rate on furnace. • Check for non-functioning zone dampers. NOTE: Limit trips will place the iHarmony zoning system into non-zone mode. NOTE: See ACC-14-01 for further details.

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.