System Diagnostics

Sort Out Rooftop Calls Without Getting Lost in the Wiring Diagram

ACLogics gives you the checks in order for economizers, phase monitors and belt-drive blowers, so you leave the roof with the cause confirmed.

FAULT SYMPTOM

Low suction pressure

CHECK 01

Measure Evaporator Temperature Drop (Delta-T). What is the temperature drop across the coil?

High Drop (Above 22°F)
DIAGNOSIS

Dirty air filter, closed supply registers, or low speed blower.

Low Drop (Below 16°F)
CHECK 02

Measure Superheat and Subcooling. What are your readings?

High Superheat, Low SubcoolingLow Superheat, High Subcooling

Complete diagnostic tree — every branch, every fault path

Try ACLogics Free — iPhone & Android

What You'll Stop Guessing About

Know what failed before you order the part.

Find Why the Economizer Misbehaves

Narrow it to a stuck damper, a bad enthalpy sensor or a binding actuator.

Keep the Blower Motor From Burning Up

Check belt tension, sheave alignment and motor amps so the motor doesn't overheat.

Catch Power Problems Before They Kill a Compressor

Check phase balance, spot single-phasing and test the contactor under load.

How a Call Goes

01

Tell It What's on the Roof

Enter size, voltage and heat type (gas or electric), so the checks fit the unit.

02

Check Safeties and Controls in Order

Work through safety circuits, freeze stats and building automation inputs, most likely first.

03

Confirm It's Performing

Check supply air temperature, static pressure and economizer operation before you leave.

Deployment

Simple, Transparent Pricing

Pick a plan when your whole team needs it on every call.

Free Plan

$0

Explore the core workflow at no cost.

Pro Plan

$14.99 /month

Built for independent experts.

Team Plan

$99 /month · up to 5 members

Standard for growing HVAC shops.

Frequently Asked Questions

The economizer stays open when it's hot outside. How do I fix it?

This usually means a failed enthalpy sensor or a stuck actuator. We guide you through testing the sensor resistance and manual positioning.

I hear a squealing noise on startup. Is it the belt?

Likely. It could be a loose belt or a sheave alignment issue. Our guide helps you measure deflection and check for pulley wear.

The unit trips on high pressure but the condenser is clean. Why?

Check for non-condensables, condenser fan rotation (especially on 3-phase), or a restriction. We help isolate the cause systematically.

Know What to Check Next on Your Next Call

Get the checks in order, confirm the cause, and fix it right the first time.