Lennox Equipment not specified Error Code 416

Equipment not specified:

What It Means

  • OD Coil Sensor Faulty

Causes & actions from Lennox

How it shows
  • iComfort S30 alert: 416

Priority condition: Service Soon The outdoor coil sensor is either open, short-circuited or the temperature is out of sensor range. • Outdoor unit control will not perform demand or time / temperature defrost operation. (System will still heat or cool.) • This fault is detected by allowing the unit to run for 90 seconds before checking sensor resistance. If the sensor resistance is not within range after 90 seconds, the control will display a moderate code. • Advances from moderate to critical after ten (10) minutes. • Plug-in sensor harness correctly. • Check resistance of sensor to determine if it is open, shorted, out of temperature calibration or out of ambient temperature range. Replace if out-of-specifications.

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.