What It Means
- OD Inverter Compressor Startup Fail

Equipment not specified:
Priority condition: Service Soon/Service Urgent Compressor start-up failure. • If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition. • Anti-short cycle is initiated. • If condition occurs 10 times within 60 consecutive minutes, the system will lockout – critical condition. • Inverter LEDs will flash code 26. • Refer to the unit service documentation for detailed troubleshooting procedures. Priority condition: Service Soon/Service Urgent Inverter flash code 26. Priority condition: Service Soon/Service Urgent The sequence is: • Red LED: Two Flashes • Green LED: Six Flashes NOTE: Inverter normal operations with no error code present is as follows. Red LED is ON and Green LED is OFF. • Check refrigerant • Replace outdoor control board • Replace inverter.
OD Inverter Compressor Startup Fail