What It Means
- OD Inverter EEPROM Checksum fault

Equipment not specified:
Priority condition: Service Urgent Inverter internal error. • When this error occurs, the outdoor control will cycle power to the inverter by opening the contactor for two minutes – moderate condition. • Outdoor control will cycle power to the inverter three times and then outdoor unit is locked out – critical condition. • Inverter LEDs will flash code 60. • Refer to the unit service documentation for detailed troubleshooting procedures. Priority condition: Service Urgent Inverter flash code 60. Priority condition: Service Urgent The sequence is: • Red LED: Six Flashes • Green LED: Off NOTE: Inverter normal operations with no error code present is as follows. Red LED is ON and Green LED is OFF.
OD Inverter EEPROM Checksum fault