Lennox Unit controller

Lennox Unit controller Error Code 109

Unit controller

What It Means

  • STRIKE 3 SUPPLY DUCT PRESSURE LIMIT

Causes & actions from Lennox

How it shows
  • M4 alarm code: 109

• Check sensor and wiring. • Unit controller shall “lock out” a unit operation after the Max Static Duct Pressure Occurrences have occurred of Supply Static Pressure Sensor Error (alarm 107) and/ or High Supply Static (Duct) Pressure (alarm 108). • User shall be able to clear supply static pressure lockout and alarm via User Interface. Supply Static Pressure lockout and alarm shall be cleared after the unit controller reset. • The number of strikes is three by default. this can be changed using Parameter 43. Optional occurrence setting is 1 to 7.

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.