What It Means
- STRIKE 3 SUPPLY DUCT PRESSURE LIMIT

Unit controller
• Check sensor and wiring. • Unit controller shall “lock out” a unit operation after the Max Static Duct Pressure Occurrences have occurred of Supply Static Pressure Sensor Error (alarm 107) and/ or High Supply Static (Duct) Pressure (alarm 108). • User shall be able to clear supply static pressure lockout and alarm via User Interface. Supply Static Pressure lockout and alarm shall be cleared after the unit controller reset. • The number of strikes is three by default. this can be changed using Parameter 43. Optional occurrence setting is 1 to 7.
STRIKE 3 SUPPLY DUCT PRESSURE LIMIT
MODEL L - M4 UNIT CONTROLLER, M4 Unit Controller