What It Means
- Unsteady thermostat input

Zone controller
This error occurs when a thermostat changes state repeatedly and rapidly, indicating that the thermostat is making intermittent contact and needs attention. The offending thermostat will be ignored for four minutes after the zone control system detects the problem. After four minutes if the signal from the thermostat is steady again, it will be recognized by the zone control system. Disconnect thermostats until error goes away. This will identify the source of bad input. If error remains after all inputs have been disconnected, replace zone control panel.
Unsteady thermostat input
HARMONY III, X9953