What It Means
- HIGH PRESSURE SWITCH COMPRESSOR 1

Unit controller
Compressor is off. Check charge, fans and coil. NOTE: On Ultra-High Efficiency units - if only alarm 12 is present then issue could be high temperature S5 switch. If alarm 12 is accompanied with alarm 14 then most likely it is the high pressure S4 switch. The unit controller will clear high pressure switch alarm when corresponding high pressure switch is detected as closed. Compressor will not restart until corresponding high pressure switch is closed and Minimum Off Delay (cooling or heating) has expired.
HIGH PRESSURE SWITCH COMPRESSOR 1
MODEL L - M4 UNIT CONTROLLER, M4 Unit Controller
Continue in ACLogics with guided diagnosis for your equipment and symptoms.