What It Means
- DAMPER STUCK CLOSED

Unit controller
• The damper is not opening to the target percentage. Unit may be bringing in less than anticipated outdoor air. • Inspect damper and / or actuator for blockage. alarm is raised when damper actuator feedback exceeds 2v under target for 2 minutes. • Alarm will reset automatically when damper feedback falls to 1.8v within the target voltage.
DAMPER STUCK CLOSED
MODEL L - M4 UNIT CONTROLLER, M4 Unit Controller