What It Means
- HIGH PRESSURE STRIKE 3 - COMPRESSOR 2

Unit controller
• Compressor lockout. Check charge, fans and coil. Use service menu to clear lockouts. • User will be able to clear high pressure switch compressor lockout and alarm via user interface. High pressure switch compressor lockout and alarm will be cleared after the CORE Unit Controller reset. • High pressure switch compressor lockout and alarm will be cleared on removal of cooling demand. • Default is 3 occurrences and can be set between 1 and 7 occurrences.
HIGH PRESSURE STRIKE 3 - COMPRESSOR 2
MODEL L - M4 UNIT CONTROLLER, M4 Unit Controller