What It Means
- BLOWER MOTOR FAULT

Unit controller
DirectPlus blower fault detected. The CORE Control System will start monitoring the motor status ten seconds after blower command is sent. The CORE Unit Controller will stop unit operation if fault conditions are detected. Fix source of fault and reset (reboot) CORE Unit Controller. NOTE: For blowers connected via MODBUS, the alarming Value = any present motor alarms. Sum of the error numbers equals the current fault, for example 48 means motor overheated (32 + 16): 1 - Phase failure (3-phase devices) or mains under voltage (1-phase devices) 4 - Power module overheated 8 - Communication error between M4 controller and blower 16 - Fan bad (general error, set with every error condition) 32 - Motor overheated 64 - Hall sensor error 128 - Locked motor 4096 - DC-link under voltage
BLOWER MOTOR FAULT
MODEL L - M4 UNIT CONTROLLER, M4 Unit Controller