What It Means
- BLOWER - NO AIRFLOW DETECTED

Unit controller
Unit off. Air flow switch is normally closed. Monitoring starts 16 seconds after blower is started. If air flow switch is detected open after 16 second delay period, all compressors are de-energized, gas valves closed, electric heat turned off, economizer damper closed, and blower is stopped. Alarm will automatically clear once the error timed off delay has expired and system will resume. Check blower operation.
BLOWER - NO AIRFLOW DETECTED
MODEL L - M4 UNIT CONTROLLER, M4 Unit Controller