Lennox Unit controller

Lennox Error Code 92

Unit controller

What It Means

  • INDOOR ENTHALPY SENSOR

Causes & actions from Lennox

How it shows
  • M4 alarm code: 92

If Enthalpy Sensor failure is detected, the system will disable ‘Free Cooling’ operation. NOTE: Valid Outdoor Enthalpy Sensor reading is required for both ‘ODE’ (Outdoor Enthalpy) and ‘ODE differential’ (Outdoor differential). Valid Indoor Enthalpy Sensor reading is required for ‘ODE differential’ (Outdoor differential). Check wiring and test A62 sensor using specified method in M4 application guide, section titled economizer checkout.

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.