Lennox Unit controller

Lennox Error Code 93

Unit controller

What It Means

  • UNIT OPERATING IN BACKUP MODE

Causes & actions from Lennox

How it shows
  • M4 alarm code: 93

• Check communication loss with network sensor or if CORE Unit Controller If NETWORK INTEGRATION is set to RTU STANDALONE MODE and backup sensor is set to RETURN AIR BACKUP. • While running in backup mode the unit controller will set this alarm. The unit controller will return from Backup mode to Primary (Main) mode on a reset or after the Primary mode (room Sensor is not in error or OR network communication is re-established and available for 300 seconds. • Backup mode alarm will be cleared on the reset OR after the unit controller has returned to primary (main) system mode.