Lennox Unit controller

Lennox Error Code 99

Unit controller

What It Means

  • OUTSIDE AIR VELOCITY SENSOR ERROR

Causes & actions from Lennox

How it shows
  • M4 alarm code: 99

Check sensor and wiring. This alarm activates when the A24 sensor input signal is continuously above 25% of sensor measuring range for more than five minutes with blower stopped. The CORE Unit Controller will disable the Outdoor Air CFM control. The alarm automatically clears when the sensor reading is below 10% sensor measuring range for one minute.