Lennox Split & Multi-Split Error Code E160

Split & Multi-Split:

What It Means

  • The refrigerant detection system sensor is of an incorrect type.

Causes & actions from Lennox

How it shows
  • Single-character display: E160

The sensor of the refrigerant detection system is of a type not suitable for use in the application. Replace the sensor with a Lennox approved replacement part. This fault clears when a sensor suitable for the application is detected by the refrigerant detection system, but will latch for a minimum of 5 minutes. Retest of the presence of the fault can be effected by pressing the RDS test button on the indoor unit control board.

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.