Lennox Split & Multi-Split Error Code E410

Split & Multi-Split

E410 means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.

What It Means

  • The outdoor unit cycled off due to low suction pressure.
  • The outdoor unit cycled off due to low pressure switch opening.
  • The outdoor unit cycled off due to low pressure protection logic.
  • s The outdoor unit cycled off due to p low pressure switch opening. c a

Causes & actions from Lennox

The outdoor unit cycled off due to low suction pressure.

40 models

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060, EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060, EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060, SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060, SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Air conditioner (outdoor), Heat pump (outdoor)

How it shows
  • Outdoor control 7-segment display: E410

Unit pressure is below the lower limit. The system is shut down. The suction pressure transducer emulates a low pressure switch, the unit does not have a low pressure switch. The cut-out is set at 40 PSIG and the cut-in set at 90 PSIG. Confirm that the system is properly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after the pressure rises above 90 PSIG.

Other manual wording (1 of 4)

SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Unit pressure is below the lower limit. The system is shut down. The cut-out is set at 25 PSIG and the cut-in set at 40 PSIG. Confirm that the system is properly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after the pressure rises above 40 PSIG.

Other manual wording (2 of 4)

SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

Unit pressure is below the lower limit. The system is shut down. The cut-out is set at 35 PSIG and the cut-in set at 80 PSIG. SL22KLV does not have a Low Pressure switch, the low pressure switch is emulated by the suction pressure transducer. Confirm that the system is properly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. Confirm the suction pressure transducer is providing the correct suction pressure reading compared to manifold gauge pressure, if not check pressure tranducer connections. The alarm clears after the pressure rises above 80 PSIG.

Other manual wording (3 of 4)

EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

Unit pressure is below the lower limit. The system is shut down. The suction pressure transducer emulates a low pressure switch, the unit does not have a low pressure switch. The cut-out is set at 35 PSIG and the cut-in set at 80 PSIG. Confirm that the system is properly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after the pressure rises above 80 PSIG.

Other manual wording (4 of 4)

EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

Unit pressure is below the lower limit. The system is shut down. The suction pressure transducer emulates a low pressure switch, the unit does not have a low pressure switch. The cut-out is set at 35 PSIG and the cut-in set at 80 PSIG. Confirm that the system is properly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after the pressure rises above 90 PSIG.

Applicable models & manual sources
  • EL18XCV

    The outdoor unit cycled off due to low suction pressure.

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 37

  • EL18XPV

    The outdoor unit cycled off due to low suction pressure.

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 37

  • EL22KCV

    The outdoor unit cycled off due to low suction pressure.

    EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060

    EL22KCV manual, page 40

  • SL25KCV

    The outdoor unit cycled off due to low suction pressure.

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 36

  • SL28XCV

    The outdoor unit cycled off due to low suction pressure.

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 30

  • SL22KLV

    The outdoor unit cycled off due to low suction pressure.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 43

  • EL21KLV

    The outdoor unit cycled off due to low suction pressure.

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 46

  • EL19KPV

    The outdoor unit cycled off due to low suction pressure.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 43

The outdoor unit cycled off due to low pressure switch opening.

25 models

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060, SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Air conditioner (outdoor), Heat pump (outdoor)

How it shows
  • Outdoor control 7-segment display: E410

Unit pressure is below the lower limit. The system is shutdown. The low pressure switch closes above 90PSIG and opens below 40PSIG. Confirm that the system is properly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after the pressure switch opens or after a power reset.

Other manual wording

EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

Unit pressure is below the lower limit. The system is shutdown. The low pressure switch closes above 80PSIG and opens below 35PSIG. Confirm that the system is properly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after the pressure switch opens or after a power reset.

Applicable models & manual sources
  • EL18XCV

    The outdoor unit cycled off due to low pressure switch opening.

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 60

  • EL18XPV

    The outdoor unit cycled off due to low pressure switch opening.

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 62

  • SL25KCV

    The outdoor unit cycled off due to low pressure switch opening.

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 57

  • SL28XCV

    The outdoor unit cycled off due to low pressure switch opening.

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 51

  • EL19KPV

    The outdoor unit cycled off due to low pressure switch opening.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 65

The outdoor unit cycled off due to low pressure protection logic.

5 models

SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

Heat pump (outdoor)

How it shows
  • Outdoor control 7-segment display: E410

Unit pressure is below the lower limit. The system is shut down. The suction pressure is below the suction pressure logic: opens below 25 PSIG and closes above 80 PSIG. Confirm that the system is properly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after the pressure protection opens or after a power reset.

Applicable models & manual sources
  • SL22KLV

    The outdoor unit cycled off due to low pressure protection logic.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 67

s The outdoor unit cycled off due to p low pressure switch opening. c a

5 models

EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

Heat pump (outdoor)

How it shows
  • Outdoor control 7-segment display: E410

Unit pressure is below the lower limit. The system is shutdown. The low pressure witch closes above 80 PSIG and opens below 35 PSIG. Confirm that the system is roperly charged with refrigerant. Check TXV, indoor unit blower motor, dirty filters or logged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears fter the pressure switch opens or after a power reset.

Applicable models & manual sources
  • EL21KLV

    s The outdoor unit cycled off due to p low pressure switch opening. c a

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 71

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.