Lennox G43UF Error Codes
Equipment type not specified · Ducted Heating
- ALTERNATING FAST FLASH The following conditions are sensed Improper main ground (control board 32M88) during the…
- ALTERNATING SLOW FLASH Watchguard -- burners failed to ignite OR: limit open more than 3 minutes (control board…
- FAST FLASH, SLOW FLASH Main power polarity reversed. Switch line and neutral.
- OFF, ON Circuit board failure or control wired incorrectly.
- OFF, SLOW FLASH Prove switch open. OR:Blocked inlet/exhaust vent; OR: Prove switch closed prior to…
- ON, OFF Circuit board failure or control wired incorrectly.
- ON, ON Circuit board failure or control wired incorrectly.
- ON, SLOW FLASH Rollout switch open. OR: 12-pin connector improperly attached.
- SIMULTANEOUS FAST FLASH Normal operation - signaled when heating demand initiated at thermostat.
- SIMULTANEOUS SLOW FLASH Power on - Normal operation. Also signaled during cooling and continuous fan.
- SLOW FLASH, FAST FLASH Low flame signal. Measures below Control board 32M88 - 0.18 microamps Control board 78M47…
- SLOW FLASH, OFF Flame sensed without gas valve energized.
- SLOW FLASH, ON Primary or secondary limit switch open. Limit must close within 3 minutes or unit goes…