- Home
- Error Codes
- Lennox
- Models
- LGM156U
Lennox LGM156U Error Codes
Packaged HVAC · Packaged Unit
Model numbers in this family: LGM156U, LGM180U, LGM210U, LGM240U, LGM300U
- 1 Flash Rollout Switch open
- 2 Flashes Limit Switch open or opened multiple times during one heating demand
- 3 Flashes Pressure Switch open with CAI ON
- 4 Flashes Control lockout - failed to detect or sustain flame
- 5 Flashes Flame sensed and gas valve not energize
- 6 Flashes Pressure Switch closed with CAI OFF
- 7 Flashes Not used
- 8 Flashes Pressure switch opened repeatedly during heating demand
- Fast Flash Normal Operation - call for heat
- Slow Flash Normal Operation - No call for heat
- Steady Off Internal control board fault or no power
- Steady On Control board failure
Reference only. Confirm against the manual for your exact model. Data release 105f66ecb9e96e5dc473025d.