Lennox ML296UHV Error Codes
Equipment type not specified · Ducted Heating
- 1 Flash Flame present with gas vavle de-energized.
- 2 Flashes Pressure switch closed with combustion air inducer de-energized.
- 3 Flashes Pressure switch open with inducer energized
- 4 Flashes Primary limit, secondarylLimit, or rollout switch open
- 5 Flashes Not used
- 6 Flashes Pressure switch cycle lockout.
- 7 Flashes Lockout, burners fail to light.
- 8 Flashes Lockout, burners lost flame too many times.
- 9 Flashes Line voltage polarity incorrect.
- Green LED Flashing High heat demand, high pressure switch not closed
- Green LED Off No demand for high heat
- Green LED On High heat demand, operating normally
- LED Off No power to control or control hardware fault detected.
- LED On Normal operation.
Reference only. Confirm against the manual for your exact model. Data release 105f66ecb9e96e5dc473025d.