Lennox Unit controller

Lennox Unit controller Error Code 13

Unit controller

What It Means

  • HIGH PRESSURE STRIKE 3 COMPRESSOR 1

Causes & actions from Lennox

How it shows
  • M4 alarm code: 13

• Compressor is lockout. Check charge, fans and coil. Use service menu to clear lockouts. • User will be able to clear high pressure switch compressor lockout and alarm via user interface. High pressure switch compressor lockout and alarm will be cleared after the CORE Unit Controller reset. • High pressure switch compressor lockout and alarm will be cleared on termination of cooling demand. • Default is 3 occurrences and can be set between 1 and 7 occurrences.