Lennox Error Code DS2 FAST Flash, DS1 ON

Split & Multi-Split:

What It Means

  • Discharge Line Temperature Discharge Sensor Lockout

Causes & actions from Lennox

How it shows
  • defrost control ds2 ds1 led: DS2 FAST Flash, DS1 ON (ds1: on, ds2: flashing (fast))

Discharge Line Temperature Discharge Sensor Lockout (5 strikes per code = LOCKOUT). This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 300ºF (148ºC) during compressor operation, the board will de-energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225ºF (107ºC).

Other manual wording

XP19

Discharge Line Temperature Discharge Sensor Lockout. (Lockout occurs after 5 strikes).

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.