What It Means
- Discharge Line Temperature Fault

Split & Multi-Split:
Discharge Line Temperature Fault. This code detects shorted sensor or high discharge temperatures. If the discharge line temperature exceeds a temperature of 300ºF (148ºC) during compressor operation, the board will de-energize the compressor contactor output (and the defrost output if active). The compressor will remain off until the discharge temperature has dropped below 225ºF (107ºC). Each fault adds 1 strike to that code's counter; 5 strikes per code = LOCKOUT.
Discharge Line Temperature Fault
Discharge Line Temperature Fault