What It Means
- SLP98UHV, SLP99UHV: LSOM - Compressor ran more than 18 hours in air conditioning mode.
- SL297UHNV: LSOM Compressor long run cycle or low system pressure.

Ducted Heating
E401 means different things on different Ducted Heating models. Enter your model number to see only your reading, or find your model below.
Models: SLP98UHV, SLP99UHV
Compressor protector is open. Check for high head pressure, check compressor supply voltage. Out- door unit power disconnect is open , compressor circuit breaker or fuse(s) is open, broken wire or connector is not making contact. Low or high pres- sure switch open if present in the system. Compres- sor contactor has failed to close.
SLP99UHV
Compressor protector is open. Check for high head pressure, check compressor supply voltage. Outdoor unit power disconnect is open , compressor circuit breaker or fuse(s) is open, broken wire or connector is not making contact. Low or high pressure switch open if present in the system. Compressor contactor has failed to close.
LSOM − Compressor ran more than 18 hours in air conditioning mode.
LSOM - Compressor ran more than 18 hours in air conditioning mode.
Models: SL297UHNV
Compressor ran more than 18 hours to satisfy a single thermostat demand. Critical Alert. Clears the error after 30 consecutive normal run cycles or power reset. Also monitors low pressure switch trips.
LSOM Compressor long run cycle or low system pressure.