Lennox Split & Multi-Split

Lennox Error Code Red Trip

Split & Multi-Split:

What It Means

  • Thermostat demand signal Y1 is present, but the compressor is not running. Heat pump only - Trip light will be on during defrost board 5 minute delay with Y thermostat call.

Causes & actions from Lennox

How it shows
  • lsom trip led: Red Trip (trip: on)

1 Compressor protector is open. 2 Outdoor unit power disconnect is open. 3 Compressor circuit breaker or fuse(s) is open. 4 Broken wire or connector is not making contact. 5 Low pressure switch open if present in the system. 6 Compressor contactor has failed to close.

Applicable models & manual sources
  • HSXB15

    Thermostat demand signal Y1 is present, but the com- pressor is not running. Heat pump only − Trip light will be on during defrost board 5 minute delay with Y thermostat call.

    HSXB15 manual, page 6

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.