What It Means
- CBK45UHPT, CBK45UHVT: Sensor indicates fault
- Long Run Time - Compressor is running extremely long run cycles.
- EL18KSLV: EEPROM malfunction

Split & Multi-Split
1 means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.
Models: CBK45UHPT, CBK45UHVT
Air handler (indoor)
Replace the sensor
CBK45UHPT, CBK45UHVT
Replace the sensor (Cat. # 26Z69)
Sensor indicates fault
Sensor indicates fault
Sensor indicates fault
Sensor indicates fault
Sensor indicates fault
Sensor indicates fault
HSXB15, XC15, XP15, XP19
1Low refrigerant charge. 2Evaporator blower is not running. (cid:4) Check blower relay coil and contacts (cid:4) Check blower motor capacitor (cid:4) Check blower motor for failure or blockage (cid:4) Check evaporator blower wiring and connectors (cid:4) Check indoor blower control board (cid:4) Check thermostat wiring for open circuit 3Evaporator coil is frozen. (cid:4) Check for low suction pressure (cid:4) Check for excessively low thermostat setting (cid:4) Check evaporator airflow (coil blockages or return air filter) (cid:4) Check ductwork or registers for blockage. 4Faulty metering device. (cid:4) Check TXV bulb installation (size, location and contact) (cid:4) Check if TXV/fixed orifice is stuck closed or defective 5Condenser coil is dirty. 6Liquid line restriction (filter drier blocked if present). 7Thermostat is malfunctioning. (cid:4) Check thermostat sub−base or wiring for short circuit (cid:4) Check thermostat installation (location and level)
XC15, XP15
1Low refrigerant charge. 2Evaporator blower is not running. 3Evaporator coil is frozen. 4Faulty metering device. 5Condenser coil is dirty. 6Liquid line restriction (filter drier blocked if present). 7Thermostat is malfunctioning.
HSXB15
1 Low refrigerant charge. 2 Evaporator blower is not running. 3 Evaporator coil is frozen. 4 Faulty metering device. 5 Condenser coil is dirty 6 Liquid line restriction (filter drier blocked if present) 7 Thermostat is malfunctioning.
Long Run Time − Compressor is running extremely long run cycles.
Long Run Time − Compressor is running extremely long run cycles.
Long Run Time − Compres- sor is running extremely long run cycles
Long Run Time − Compres- sor is running extremely long run cycles
Long Run Time Compressor is running extremely long run cycles
Models: EL18KSLV
Heat pump (outdoor)
EEPROM chip damaged or data wrong or related circuit damaged
EEPROM malfunction
Continue in ACLogics with guided diagnosis for your equipment and symptoms.