Lennox Split & Multi-Split

Lennox Split & Multi-Split Error Code 3

Split & Multi-Split

3 means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.

What It Means

  • CBK45UHPT, CBK45UHVT: Incompatible sensor type
  • Short Cycling - Compressor is running only briefly
  • EL18KSLV: Compressor drive module AC input over current

Causes & actions from Lennox

Incompatible sensor type

Models: CBK45UHPT, CBK45UHVT

Air handler (indoor)

How it shows
  • rds noncomm red flash led: 3 (red: flashing ×3)

Replace the sensor

Other manual wording (1 of 2)

CBK45UHVT

Replace with a compati- ble sensor (Cat. # 26Z69)

Other manual wording (2 of 2)

CBK45UHPT

Replace with a com- patible sensor (Cat. # 26Z69)

Applicable models & manual sources

Short Cycling - Compressor is running only briefly

4 models

HSXB15, XC15, XP15, XP19

How it shows
  • lsom alert led: 3 (alert: flashing ×3)

1Thermostat demand signal is intermittent. 2Time delay relay or control board is defective. 3If high pressure switch is present, see Flash Code 2 information.

Other manual wording (1 of 3)

HSXB15

1 Thermostat demand signal is intermittent. 2 Time delay relay or control board is defective. 3 If high pressure switch is present, check Flash Code 2 information. 4 If low pressure switch is present, check Flash Code 1 information.

Other manual wording (2 of 3)

XP15

1Thermostat demand signal is intermittent. 2Time delay relay or DCB is defective. 3If high pressure switch is present, see Flash Code 2 information. 4If low pressure switch is present, see Flash Code 2 information.

Other manual wording (3 of 3)

XC15

1Thermostat demand signal is intermittent. 2Time delay relay or control board is defective. 3If high pressure switch is present, see Flash Code 2 information. 4If low pressure switch is present, see Flash Code 1 information.

Applicable models & manual sources

Compressor drive module AC input over current

Models: EL18KSLV

Heat pump (outdoor)

How it shows
  • el18kslv outdoor fault display: 3
  • el18kslv pcb fault led: 3

AC Input over current been detected by compressor drive module or input current higher than main board setting.

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.