Lennox Ducted Heating

Lennox Error Code 4 flashes

Ducted Heating:

What It Means

  • Before ignition: Hi limit CLOSED? NO: check main valve OFF; hold until hi limit closes. During operation: rollout CLOSED? NO: lockout main valve OFF, combustion/system fans ON; reset or replace rollout switch. During operation hi limit CLOSED? NO: main valve OFF, combustion/system fans ON; hold until switch closes. These three conditional branches are separate.

Causes & actions from Lennox

How it shows
  • ram diagnostic led: 4 flashes

Hi limit switch or rollout switch open. Sequence holds until switch closes, or lockout occurs on rollout switch trip.

Applicable models & manual sources
  • G24M

    Before ignition: Hi limit CLOSED? NO: check main valve OFF; hold until hi limit closes. During operation: rollout CLOSED? NO: lockout main valve OFF, combustion/system fans ON; reset or replace rollout switch. During operation hi limit CLOSED? NO: main valve OFF, combustion/system fans ON; hold until switch closes. These three conditional branches are separate.

    G24M manual, page 24

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.

What should you check next?

Continue in ACLogics with guided diagnosis for your equipment and symptoms.

See how guided diagnosis works →