What It Means
- OD EIM W Output Hardware Fault

Equipment not specified:
Priority condition: Service Soon There is a faulty W output circuit. • W terminal is energized while in cooling mode. • Possible cause may be a stuck closed relay on the control, or something external to the control that is energizing W terminal when it should not be energized. • Disconnect any wiring from the W terminal. • If 24VAC is still present on the terminal, then it is a stuck relay. • If 24VAC disappears, then there is a need to check any of the wires hooked up to the W terminal.
OD EIM W Output Hardware Fault
Continue in ACLogics with guided diagnosis for your equipment and symptoms.