Lennox Error Code DS2 OFF, DS1 OFF

Split & Multi-Split: Heat pump (outdoor)

What It Means

  • Power problem

Causes & actions from Lennox

How it shows
  • defrost control ds2 ds1 led: DS2 OFF, DS1 OFF (ds1: off, ds2: off)
  • defrost control ds2 ds1 led: DS2 OFF, DS1 OFF (ds1: off, ds2: off)

No power (24V) to demand defrost control terminals R and C or demand defrost control failure. 1. Check control transformer power (24V). 2. If power is available to demand defrost control and LEDs do not light, replace demand defrost control.

Other manual wording (1 of 2)

XP19

1Check control transformer power (24V). 2If power is available to board and LED(s) do not light, replace board.

Other manual wording (2 of 2)

XP15

1Check control transformer power (24V). 2If power is available to DCB and LED(s) do not light, replace DCB.

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.