Lennox Split & Multi-Split

Lennox Error Code DS2 SLOW FLASH, DS1 OFF

Split & Multi-Split:

What It Means

  • High pressure fault

Causes & actions from Lennox

How it shows
  • defrost control ds2 ds1 led: DS2 SLOW FLASH, DS1 OFF (ds1: off, ds2: flashing (slow))

1Remove any blockages or restrictions from coils and/or fans. Check indoor and outdoor fan motor for proper current draws. 2Check system charge using approach and subcooling temperatures. 3Check system operating pressures and compare to unit charging charts. 4Make sure all pressure switches and sensors have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements.

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.