What It Means
- SL280DFNV, SL280UHV, SL297UHNV: Outdoor air temperature sensor failure. Only shown if shorted or out-ofrange.
- SLP98UHV, SLP99UHV: Outdoor air sensor failure - NO error if disconnected. Only shown if shorted or out-of-range.

Ducted Heating
E180 means different things on different Ducted Heating models. Enter your model number to see only your reading, or find your model below.
Models: SL280DFNV, SL280UHV, SL297UHNV
Compare outdoor sensor resistance to temperature/ resis- tance charts in unit installation instructions. Replace sensor pack if necessary. At beginning of (any) configuration, furnace or air handler control will sense outdoor air and discharge air temperature sensor(s). If detected (reading in range), appropriate feature will be set as ‘installed’ and that could be seen in ‘About’ screen. In normal operation after control recognizes sensors, alarm will be sent if valid temperature reading is lost. To get rid of setting and alarm, redo configu- ration and make sure that temperature sensor is marked as ‘not installed’ in Indoor Unit ‘About’ screen. When Indoor unit control is replaced, thermostat will ‘tell’ new control if tem- perature sensor is in system or not. Clears 30 seconds after fault recovered.
Outdoor air temperature sensor failure. Only shown if shorted or out-ofrange.
Outdoor air temperature sensor failure. Only shown if shorted or out-ofrange.
Outdoor air temperature sensor failure. Only shown if shorted or out-ofrange.
Models: SLP98UHV, SLP99UHV
Compare outdoor sensor resistance to temperature resistance charts in installation instructions. Replace if necessary.
SLP99UHV
This manual entry does not list further causes or actions.
Outdoor air sensor failure − NO error if disconnected. Only shown if shorted or out−of−range.
Outdoor air sensor failure - NO error if disconnected. Only shown if shorted or out-of-range.