Lennox Ducted Heating

Lennox Error Code E224

Ducted Heating

E224 means different things on different Ducted Heating models. Enter your model number to see only your reading, or find your model below.

What It Means

  • Low pressure switch failed closed.
  • Pressure switch failed closed.
  • SLP98UHV, SLP99UHV: Low pressure switch failed closed - Refer to troubleshooting in installation instruction.

Causes & actions from Lennox

Low pressure switch failed closed.

16 models

EL280UHE(X), EL280UHEK, EL280UHEK(X), EL296UHE, EL297UHEK, ML296UHVK, ML297UH045XV36BK, ML297UH070XV36BK, ML297UH090XV36CK, ML297UH090XV60CK, ML297UH110XV60CK, ML297UH135XV60DK, ML297UHVK, SL280DFNV, SL280UHV, SL297UHNV

Gas furnace (indoor)

How it shows
  • Integrated control 7-segment display: E224

Check operation of low pressure switch to see if it is stuck closed on heat call longer than 150 seconds. Measure oper- ating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes nor- mal operation after fault is cleared.

Other manual wording (1 of 2)

SL280DFNV, SL280UHV, SL297UHNV

Check operation of low pressure switch to see if it is stuck closed on heat call longer than 150 seconds. Mea- sure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restric- tion. Resumes normal operation after fault is cleared.

Other manual wording (2 of 2)

EL280UHE(X), EL296UHE

Check pressure (inches w.c.) of low pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

Applicable models & manual sources

Pressure switch failed closed.

8 models

EL180UHNE(K), EL195UHNEK, EL195UHNEK-01, EL195UHNEK-02, EL196UHEK, ML180UHVK, ML193DFEK, ML196UHEK

Gas furnace (indoor)

How it shows
  • Integrated control 7-segment display: E224

Check pressure (inches w.c.) of pressure switch closing on heat call. Measure operating pressure (inches w.c.). Inspect vent and combustion air inducer for correct operation and restriction. Resumes normal operation after fault is cleared.

Applicable models & manual sources

Low pressure switch failed closed - Refer to troubleshooting in installation instruction.

Models: SLP98UHV, SLP99UHV

How it shows
  • Integrated control 7-segment display: E224

Check low pressure switch for closed contacts, measure inches of water column of operating pressure, inspect vent and combustion air inducer for correct operation and re- striction.

Other manual wording

SLP99UHV

Check low pressure switch for closed contacts, measure inches of water column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.

Applicable models & manual sources
  • SLP98UHV

    Low pressure switch failed closed − Refer to troubleshooting in installation instruc- tion.

    SLP98UHV manual, page 63

  • SLP99UHV

    Low pressure switch failed closed - Refer to troubleshooting in installation instruction.

    SLP99UHV manual, page 31

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.