Lennox Error Code E411

Split & Multi-Split

E411 means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.

What It Means

  • The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.
  • The low pressure switch has opened 5 times within one hour. As a result, the outdoor unit is locked out.
  • L The low pressure switch has opened 5 times within one hour. As c a result, the outdoor unit is locked out. T
  • The low pressure protection has opened 5 times within one hour. As a result, the outdoor unit is locked out.

Causes & actions from Lennox

The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

40 models

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060, EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060, EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060, SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060, SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Air conditioner (outdoor), Heat pump (outdoor)

How it shows
  • Outdoor control 7-segment display: E411

Low pressure fault error count reached 5 strikes. The low pressure cut-out is at 40PSIG and resets at 90PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after a power reset.

Other manual wording (1 of 4)

SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Low pressure fault error count reached 5 strikes. The low pressure cut-out is at 25PSIG and resets at 40PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after a power reset.

Other manual wording (2 of 4)

SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

Low pressure fault error count reached 5 strikes. The low pressure cut-out is at 25PSIG and resets at 40PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. Confirm the suction pressure transducer is providing the correct suction pressure reading compared to manifold gauge pressure, if not check pressure tranducer connections. The alarm clears after a power reset.

Other manual wording (3 of 4)

EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

Low pressure fault error count reached 5 strikes. The low pressure cut-out is at 35 PSIG and resets at 80 PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after a power reset.

Other manual wording (4 of 4)

EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

Low pressure fault error count reached 5 strikes. The low pressure cut-out is at 35PSIG and resets at 80PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after a power reset.

Applicable models & manual sources
  • EL18XCV

    The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 37

  • EL18XPV

    The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 37

  • EL22KCV

    The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

    EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060

    EL22KCV manual, page 40

  • SL25KCV

    The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 36

  • SL28XCV

    The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 30

  • SL22KLV

    The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 43

  • EL21KLV

    The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 46

  • EL19KPV

    The low pressure fault has occurred 5 times within one hour. As a result, the outdoor unit is locked out.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 43

The low pressure switch has opened 5 times within one hour. As a result, the outdoor unit is locked out.

25 models

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060, SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Air conditioner (outdoor), Heat pump (outdoor)

How it shows
  • Outdoor control 7-segment display: E411

Low pressure switch error count reached 5 strikes. The low pressure switch for HFC410A opens at 40PSIG and resets at 90PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after a power reset.

Other manual wording

EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

Low pressure switch error count reached 5 strikes. The low pressure switch for R454B opens at 35PSIG and resets at 80PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after a power reset.

Applicable models & manual sources
  • EL18XCV

    The low pressure switch has opened 5 times within one hour. As a result, the outdoor unit is locked out.

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 60

  • EL18XPV

    The low pressure switch has opened 5 times within one hour. As a result, the outdoor unit is locked out.

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 62

  • SL25KCV

    The low pressure switch has opened 5 times within one hour. As a result, the outdoor unit is locked out.

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 57

  • SL28XCV

    The low pressure switch has opened 5 times within one hour. As a result, the outdoor unit is locked out.

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 51

  • EL19KPV

    The low pressure switch has opened 5 times within one hour. As a result, the outdoor unit is locked out.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 65

L The low pressure switch has opened 5 times within one hour. As c a result, the outdoor unit is locked out. T

5 models

EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

Heat pump (outdoor)

How it shows
  • Outdoor control 7-segment display: E411

ow pressure switch error count reached 5 strikes. The low pressure switch for R454B opens at 35 PSIG and resets at 80 PSIG. Confirm that the system is properly harged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. he alarm clears after a power reset.

Applicable models & manual sources
  • EL21KLV

    L The low pressure switch has opened 5 times within one hour. As c a result, the outdoor unit is locked out. T

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 71

The low pressure protection has opened 5 times within one hour. As a result, the outdoor unit is locked out.

5 models

SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

Heat pump (outdoor)

How it shows
  • Outdoor control 7-segment display: E411

Low pressure protection error count reached 5 strikes. The low pressure protection for R454B opens at 25PSIG and resets at 80PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, dirty filters or clogged refrigerant filter. Confirm that the evaporator coil is clean. The alarm clears after a power reset.

Applicable models & manual sources
  • SL22KLV

    The low pressure protection has opened 5 times within one hour. As a result, the outdoor unit is locked out.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 67