What It Means
- The outdoor unit high pressure switch has opened.
- o c The outdoor unit high pressure switch has opened. c F s

Split & Multi-Split
E412 means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.
EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060, EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060, EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060, SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060, SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060
Air conditioner (outdoor), Heat pump (outdoor)
Unit pressure is above the upper limit. System is shut down. The high pressure switch opens at 590PSIG and closes at 418PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, clogged refrigerant filter. Confirm that the outdoor unit is clean. The alarm clears after the pressure switch closes or a power reset. For heating, indoor CFM may be set too low. For zoning system, zone CFM may be set too low.
EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060
Unit pressure is above the upper limit. System is shut down. The high pressure switch opens at 590 PSIG and closes at 418 PSIG. Confirm that the system is properly charged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, clogged refrigerant filter. Confirm that the outdoor unit is clean. The alarm clears after the pressure switch closes or a power reset. For heating, indoor CFM may be set too low. For zoning system, zone CFM may be set too low.
The outdoor unit high pressure switch has opened.
EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060
The outdoor unit high pressure switch has opened.
EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060
The outdoor unit high pressure switch has opened.
EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060
The outdoor unit high pressure switch has opened.
EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060
The outdoor unit high pressure switch has opened.
EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060
The outdoor unit high pressure switch has opened.
EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060
The outdoor unit high pressure switch has opened.
EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060
The outdoor unit high pressure switch has opened.
EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060
The outdoor unit high pressure switch has opened.
SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060
The outdoor unit high pressure switch has opened.
SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060
The outdoor unit high pressure switch has opened.
SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060
The outdoor unit high pressure switch has opened.
SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060
The outdoor unit high pressure switch has opened.
SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060
The outdoor unit high pressure switch has opened.
SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060
The outdoor unit high pressure switch has opened.
EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060
EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060
Heat pump (outdoor)
Unit pressure is above the upper limit. System is shut down. The high pressure switch pens at 590 PSIG and closes at 418 PSIG. Confirm that the system is properly harged with refrigerant. Check for clogged TXV, blockage to indoor unit blower motor, clogged refrigerant filter. Confirm that the outdoor unit is clean. The alarm lears after the pressure switch closes or a power reset. or heating, indoor CFM may be set too low. For zoning system, zone CFM may be et too low.
o c The outdoor unit high pressure switch has opened. c F s
EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060