- EL18XCV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060
EL18XCV manual, page 38
EL18XCV manual, page 76
- EL18XPV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060
EL18XPV manual, page 38
EL18XPV manual, page 79
- EL19KPV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060
EL19KPV manual, page 44
EL19KPV manual, page 44
- EL19KPV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060
EL19KPV manual, page 81
EL19KPV manual, page 81
- EL22KCV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060
EL22KCV manual, page 41
EL22KCV manual, page 41
EL22KCV manual, page 76
- SL22KLV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060
SL22KLV manual, page 44
- SL22KLV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060
SL22KLV manual, page 87
- SL25KCV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060
SL25KCV manual, page 38
SL25KCV manual, page 71
- SL28XCV
On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060
SL28XCV manual, page 32
SL28XCV manual, page 65