Lennox Error Code E429

Split & Multi-Split

E429 means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.

What It Means

  • On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
  • On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a Service Soon code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a Service Urgent code.

Causes & actions from Lennox

On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

35 models

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060, EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060, SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060, SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Air conditioner (outdoor), Heat pump (outdoor)

How it shows
  • Inverter code: 23
  • Inverter LED flash code: Red 2 flashes, Green 3 flashes (green: flashing ×3, red: flashing ×2)
  • Outdoor control 7-segment display: E429

Issues: (1) If DC link power in inverter does not rise above 180 VDC for 2- and 3-ton models, 250 VDC for 4- and 5-ton models, within 30 seconds, the outdoor control will display a moderate code. (2) Capacitors on inverter do not properly charge. Corrective Actions: (1) Check for proper main power to outdoor unit and for any loose electrical connections.

Applicable models & manual sources
  • EL18XCV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 38

    EL18XCV manual, page 76

  • EL18XPV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 38

    EL18XPV manual, page 79

  • EL19KPV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 44

    EL19KPV manual, page 44

  • EL19KPV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 81

    EL19KPV manual, page 81

  • EL22KCV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060

    EL22KCV manual, page 41

    EL22KCV manual, page 41

    EL22KCV manual, page 76

  • SL22KLV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 44

  • SL22KLV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 87

  • SL25KCV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 38

    SL25KCV manual, page 71

  • SL28XCV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 32

    SL28XCV manual, page 65

On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a Service Soon code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a Service Urgent code.

5 models

EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

Heat pump (outdoor)

How it shows
  • Inverter code: 23
  • Inverter LED flash code: Red 2 flashes, Green 3 flashes (green: flashing ×3, red: flashing ×2)
  • Outdoor control 7-segment display: E429

Issues: (1) If DC link power in inverter does not rise above 180 VDC for 2- and 3-ton models, 250 VDC for 4- and 5-ton models, within 30 seconds, the outdoor control will display a Service Soon code. (2) Capacitors on inverter do not properly charge. Corrective Actions: (1) Check for proper main power to outdoor unit and for any loose electrical connections.

Applicable models & manual sources
  • EL21KLV

    On a call for compressor operation, if DC link power in inverter does not rise above 180 VDC for 2 and 3 ton models, 250 VDC for 4 and 5 ton models, within 30 seconds, the control will display a Service Soon code. If condition is detected, outdoor unit will stop (Compressor and fan). Antishort cycles is initiated. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a Service Urgent code.

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 47

    EL21KLV manual, page 47

    EL21KLV manual, page 93

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.