Lennox Error Code E431

Split & Multi-Split

E431 means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.

What It Means

  • Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.
  • Error occurs when PFC detects an over-current condition of 100A, the control will display a Service Soon code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a Service Urgent code.

Causes & actions from Lennox

Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

35 models

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060, EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060, SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060, SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Air conditioner (outdoor), Heat pump (outdoor)

How it shows
  • Inverter code: 27
  • Inverter LED flash code: Red 2 flashes, Green 7 flashes (green: flashing ×7, red: flashing ×2)
  • Outdoor control 7-segment display: E431

Issues: (1) Indicates power interruption, brownout, poor electrical connection or loose inverter input wire. (2) System testing was set up and code was generated when the reversing valve is de-energized coming out of defrost (code appears with or without 30 compressor delay). Corrective Actions: (1) Check for proper main power to outdoor unit and for any loose electrical connections.

Other manual wording

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV,…

Issues: (1) Indicates power interruption, brownout, poor electrical connection or loose inverter input wire. (2) System testing was set up and code was generated when the reversing valve is de-energized coming out of defrost (code appears with or without 30 compressor delay). Corrective Actions: (1) Check for proper main power to outdoor unit and for any loose electrical connections. (2) To clear, disconnect power to the indoor unit (24VAC power source to the outdoor control) which will power off the outdoor control and will open the outdoor unit contactor, which interrupts power to the inverter and then re-apply power.

Applicable models & manual sources
  • EL18XCV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 77

  • EL18XPV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 80

  • EL19KPV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 82

    EL19KPV manual, page 82

  • EL22KCV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060

    EL22KCV manual, page 77

  • SL22KLV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 87

  • SL25KCV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 72

  • SL28XCV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 66

  • EL18XCV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti- short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 38

  • EL18XPV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti- short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 38

  • EL19KPV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti- short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 44

    EL19KPV manual, page 44

  • EL22KCV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti- short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060

    EL22KCV manual, page 41

    EL22KCV manual, page 41

  • SL22KLV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti- short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 44

  • SL25KCV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti- short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 38

  • SL28XCV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a moderate code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti- short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a critical code.

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 32

Error occurs when PFC detects an over-current condition of 100A, the control will display a Service Soon code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a Service Urgent code.

5 models

EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

Heat pump (outdoor)

How it shows
  • Inverter code: 27
  • Inverter LED flash code: Red 2 flashes, Green 7 flashes (green: flashing ×7, red: flashing ×2)
  • Outdoor control 7-segment display: E431

Issues: (1) Indicates power interruption, brownout, poor electrical connection or loose inverter input wire. (2) System testing was set up and code was generated when the reversing valve is de-energized coming out of defrost (code appears with or without 30 compressor delay). Corrective Actions: (1) Check for proper main power to outdoor unit and for any loose electrical connections.

Other manual wording

EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

Issues: (1) Indicates power interruption, brownout, poor electrical connection or loose inverter input wire. (2) System testing was set up and code was generated when the reversing valve is de-energized coming out of defrost (code appears with or without 30 compressor delay). Corrective Actions: (1) Check for proper main power to outdoor unit and for any loose electrical connections. (2) To clear, disconnect power to the indoor unit (24VAC power source to the outdoor control) which will power off the outdoor control and will open the outdoor unit contactor, which interrupts power to the inverter and then re-apply power.

Applicable models & manual sources
  • EL21KLV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a service soon code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a service urgent code.

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 94

    EL21KLV manual, page 94

  • EL21KLV

    Error occurs when PFC detects an over-current condition of 100A, the control will display a Service Soon code. If condition is detected, outdoor unit will stop (Compressor and fan). Anti-short cycle is initiated. Inverter is unavailable to communicate with the outdoor control for 3 minutes. If condition occurs 10 times within a 60 minute rolling time period, system will lock out and display a Service Urgent code.

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 47

    EL21KLV manual, page 47

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.