Lennox Split & Multi-Split

Lennox Error Code E441

Split & Multi-Split

E441 means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.

What It Means

  • Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.
  • 3WPD036S6S-1P: Cooling operation restricted at outdoor temperature below Tcool_low value (default:0°C)

Causes & actions from Lennox

Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

40 models

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060, EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060, EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060, SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060, SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060, SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

Air conditioner (outdoor), Heat pump (outdoor)

How it shows
  • Inverter code: 14
  • Inverter LED flash code: Red 1 flash, Green 4 flashes (green: flashing ×4, red: flashing ×1)
  • Outdoor control 7-segment display: E441

This error code is primarily for informational purposes as the inverter controls the compressor to operate within design parameters. Alert code 441 typically occurs at startup as the compressor as the currently increases rapidly during startup. The inverter will reduce the compressor speed by 4 hz and slow the compressor ramp up speed to the requested compressor demand (capacity). This is normal and expected operation of the inverter to control the compressor within design parameters. In most cases the alert code 441 does not require any additional service or diagnostic procedures. E441 may also occur if the system is operating at high pressures.

Other manual wording (1 of 2)

EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060, EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060, EL19KPV,…

This error code is primarily for informational purposes as the inverter controls the compressor to operate within design parameters. Alert code 441 typically occurs at startup as the compressor as the currently increases rapidly during startup. The inverter will reduce the compressor speed by 4 hz and slow the compressor ramp up speed to the requested compressor demand (capacity). This is normal and expected operation of the inverter to control the compressor within design parameters. In most cases the alert code 441 does not require any additional service or diagnostic procedures. E441 may also occur if the system is operating at high pressures. This error code is primarily for informational purposes as the inverter controls the compressor to operate within design parameters. Alert code 441 typically occurs at startup as the compressor as the currently increases rapidly during startup. The inverter will reduce the compressor speed by 4 hz and slow the compressor ramp up speed to the requested compressor demand (capacity). This is normal and expected operation of the inverter to control the compressor within design parameters. In most cases the alert code 441 does not require any additional service or diagnostic procedures. E441 may also occur if the system is operating at high pressures.

Other manual wording (2 of 2)

SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

This error code is primarily for informational purposes as the inverter controls the compressor to operate within design parameters. Alert code 441 typically occurs at startup as the compressor as the currently increases rapidly during startup. The inverter will reduce the compressor speed by 4 hz and slow the compressor ramp up speed to the requested SL25KCV demand (capacity). This is normal and expected operation of the inverter to control the compressor within design parameters. In most cases the alert code 441 does not require any additional service or diagnostic procedures. E441 may also occur if the system is operating at high pressures.

Applicable models & manual sources
  • EL18XCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 40

  • EL18XCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 63

  • EL18XPV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 65

  • EL18XPV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 40

  • EL19KPV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 46

  • EL19KPV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 68

  • EL21KLV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 49

  • EL21KLV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 74

  • EL22KCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared

    EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060

    EL22KCV manual, page 65

  • EL22KCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

    EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060

    EL22KCV manual, page 43

  • SL22KLV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 46

  • SL22KLV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 70

  • SL25KCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 40

  • SL28XCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared.

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 34

  • SL28XCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 54

  • EL18XCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared..

    EL18XCV, EL18XCV-024, EL18XCV-036, EL18XCV-048, EL18XCV-060

    EL18XCV manual, page 80

  • EL18XPV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared..

    EL18XPV, EL18XPV-024, EL18XPV-036, EL18XPV-048, EL18XPV-060

    EL18XPV manual, page 83

    EL18XPV manual, page 83

  • EL19KPV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared..

    EL19KPV, EL19KPV-024, EL19KPV-036, EL19KPV-048, EL19KPV-060

    EL19KPV manual, page 84

  • EL21KLV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared..

    EL21KLV, EL21KLV-024, EL21KLV-036, EL21KLV-048, EL21KLV-060

    EL21KLV manual, page 97

  • EL22KCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared..

    EL22KCV, EL22KCV-024, EL22KCV-036, EL22KCV-048, EL22KCV-060

    EL22KCV manual, page 80

  • SL22KLV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared..

    SL22KLV, SL22KLV-024, SL22KLV-036, SL22KLV-048, SL22KLV-060

    SL22KLV manual, page 91

  • SL25KCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared..

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 75

    SL25KCV manual, page 75

  • SL28XCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared..

    SL28XCV, SL28XCV-024, SL28XCV-036, SL28XCV-048, SL28XCV-060

    SL28XCV manual, page 69

  • SL25KCV

    Compressor slowdown due to high compressor current. Compressor current is approaching limit. The compressor speed automatically slows. The control sets indoor CFM and outdoor RPM to values according to demand percentage rather than the actual Hz. Alarm is automatically cleared

    SL25KCV, SL25KCV-024, SL25KCV-036, SL25KCV-048, SL25KCV-060

    SL25KCV manual, page 60

Cooling operation restricted at outdoor temperature below Tcool_low value (default:0°C)

Models: 3WPD036S6S-1P

Mini-split unit (outdoor)

How it shows
  • mini outdoor inverter pcb: E441
  • Mini-split outdoor main board: E441

1. C heck the range of temperature limited for cooling operation 2. C heck the outdoor temperature sensor

Applicable models & manual sources
Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.