Lennox Ducted Heating

Lennox Error Code LED#1-Off, LED#2-Slow Flash

Ducted Heating

LED#1-Off, LED#2-Slow Flash means different things on different Ducted Heating models. Enter your model number to see only your reading, or find your model below.

What It Means

  • G24M: 3.2 - Unit operates with a cooling and continuous fan demand. - Combustion air blower will not start with a Heating demand. -- Diagnostic lights flash the pressure switch failure code. LED#1-Off, LED#2-Slow Flash
  • G24M: 3.3 - Unit operates with a cooling and continuous fan demand. - Combustion air blower will not start with a Heating demand. - Diagnostic lights flash the pressure switch failure code 22.55 minutes after heating demand. LED#1-Off, LED#2-Slow Flash
  • G24M: 4.1 - Unit operates with a cooling and continuous fan demand. - Combustion air blower energizes with aa heating demand. - Diagnostic lights flash the pressure switch failure code 2.5 minutes after heatingg demand. LED##11-Off LED#2-Slow Flash
  • G24M: 6.1 - Burners fire with a heating demand. - Burners light but unit shuts off prior to satisfying T-stat demand. - Diagnostic lights flash the pressure switch code. LED#1-Off LED#2-Slow Flash

Causes & actions from Lennox

3.2 - Unit operates with a cooling and continuous fan demand. - Combustion air blower will not start with a Heating demand. -- Diagnostic lights flash the pressure switch failure code. LED#1-Off, LED#2-Slow Flash

Models: G24M

How it shows
  • SureLight board LEDs (DS1/DS2): LED#1-Off, LED#2-Slow Flash (led1: off, led2: flashing (slow))

Possible cause: 3.2.1 Miswiring of furnace or improper con- nections to combustion air blower. Corresponding action/comments: ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections. Possible cause: 3.2.2 Pressure switch stuck closed. Corresponding action/comments: ACTION 1 − Check that the pressure switch is open without the combustion air blower operat- ing. Replace if malfunctioning

Applicable models & manual sources
  • G24M

    3.2 − Unit operates with a cooling and con- tinuous fan demand. − Combustion air blower will not start with a Heating demand. −− Diagnostic lights flash the pressure switch failure code. LED#1−Off, LED#2−Slow Flash

    G24M manual, page 32

3.3 - Unit operates with a cooling and continuous fan demand. - Combustion air blower will not start with a Heating demand. - Diagnostic lights flash the pressure switch failure code 22.55 minutes after heating demand. LED#1-Off, LED#2-Slow Flash

Models: G24M

How it shows
  • SureLight board LEDs (DS1/DS2): LED#1-Off, LED#2-Slow Flash (led1: off, led2: flashing (slow))

Possible cause: 3.3.1 Miswiring of furnace or improper con- nections to combustion air blower. Corresponding action/comments: ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections. Possible cause: 3.3.2 Combustion air blower failure. Corresponding action/comments: ACTION 1 − If there is 120V to combustion air blower and it does not operate, replace combus- tion air blower.

Applicable models & manual sources
  • G24M

    3.3 − Unit operates with a cooling and con- tinuous fan demand. − Combustion air blower will not start with a Heating demand. − Diagnostic lights flash the pressure switch failure code 22.55 minutes after heating demand. LED#1−Off, LED#2−Slow Flash

    G24M manual, page 33

4.1 - Unit operates with a cooling and continuous fan demand. - Combustion air blower energizes with aa heating demand. - Diagnostic lights flash the pressure switch failure code 2.5 minutes after heatingg demand. LED##11-Off LED#2-Slow Flash

Models: G24M

How it shows
  • SureLight board LEDs (DS1/DS2): LED#1-Off, LED#2-Slow Flash (led1: off, led2: flashing (slow))

Possible cause: 4.1.1 Pressure switch does not close due to incorrect routing of the pressure switch lines. Corresponding action/comments: ACTION 1 − Check that the pressure switch lines are correctly routed. Correctly route pressure switch lines. Possible cause: 4.1.2 Pressure switch does not close due to obstructions in the pressure lines. Corresponding action/comments: ACTION 1 − Remove any obstructions from the the pressure lines and/or taps. Possible cause: 4.1.3 Pressure switch lines damaged Corresponding action/comments: ACTION 1 − Check pressure switch lines for leaks. Replace any broken lines. Possible cause: 4.1.4 Pressure switch does not close due to a low differential pressure across the pressure switch. Corresponding action/comments: ACTION 1 − Check the differential pressure across the pressure switch. This pressure should exceed the set point listed on the switch. ACTION 2 − Check for restricted inlet and ex- haust vent. Remove all blockage. ACTION 3 − Check for proper vent sizing and run length. See installation instructions. ACTION 4 − Check voltage to thre combustion air blower. Possible cause: 4.1.5 Wrong pressure switch installed in the unit, or pressure switch is out of calibration. Corresponding action/comments: ACTION 1 − Check that the proper pressure switch is installed in the unit. Replace pressure switch if necessary. Possible cause: 4.1.6 Miswiring of furnace or improper con- nections at pressure switch. Corresponding action/comments: ACTION 1 − Check for correct wiring and loose connections. Correct wiring and/or replace any loose connections. Possible cause: 4.1.7 Pressure switch failure. Corresponding action/comments: ACTION 1 − If all the above modes of failure have been checked, the pressure switch may have failed. Replace pressure switch and determine if unit will operate.

Applicable models & manual sources
  • G24M

    4.1 − Unit operates with a cooling and continuous fan demand. − Combustion air blower energizes with aa heating demand. − Diagnostic lights flash the pressure switch failure code 2.5 minutes after heatingg demand. LED##11−Off LED#2−Slow Flash

    G24M manual, page 33

6.1 - Burners fire with a heating demand. - Burners light but unit shuts off prior to satisfying T-stat demand. - Diagnostic lights flash the pressure switch code. LED#1-Off LED#2-Slow Flash

Models: G24M

How it shows
  • SureLight board LEDs (DS1/DS2): LED#1-Off, LED#2-Slow Flash (led1: off, led2: flashing (slow))

Possible cause: 6.1.1 Low pressure differential at the pres- sure switch. Corresponding action/comments: ACTION 1 − Check for restricted vent inlet or ex- haust. Remove all blockage. ACTION 2: Check for proper vent sizing. See installation instructions.

Applicable models & manual sources
  • G24M

    6.1 − Burners fire with a heating de- mand. − Burners light but unit shuts off prior to satisfying T−stat demand. − Diagnostic lights flash the pressure switch code. LED#1−Off LED#2−Slow Flash

    G24M manual, page 34

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.