Lennox Ducted Heating

Lennox Error Code LED #1 Slow Flash / LED #2 ON

Ducted Heating:

What It Means

  • Primary/secondary limit CLOSED? NO: gas valve de-energized, combustion inducer de-energized, indoor blower ON until switch closes. LED1 SLOW flash AND LED2 ON. Failed limit-reset branch enters limit Watchguard: gas valve/inducer OFF, indoor blower OFF with delay;60minute reset. Table2 board limits:63K8901/24L85 limit must close within5ignition trials;56L83/97L48 must close within3minutes. Keep board conditions distinct.

Causes & actions from Lennox

How it shows
  • SureLight board LEDs (DS1/DS2): LED #1 Slow Flash / LED #2 ON (led1: flashing (slow), led2: on)

Primary or secondary limit switch open. Gas valve de-energized, combustion air inducer de-energized, indoor blower on until switch closes. Also indicates Limit Switch Watchguard mode (gas valve off, comb. air inducer off, indoor blower off with delay).

Applicable models & manual sources
  • G24M

    Primary/secondary limit CLOSED? NO: gas valve de-energized, combustion inducer de-energized, indoor blower ON until switch closes. LED1 SLOW flash AND LED2 ON. Failed limit-reset branch enters limit Watchguard: gas valve/inducer OFF, indoor blower OFF with delay;60minute reset. Table2 board limits:63K8901/24L85 limit must close within5ignition trials;56L83/97L48 must close within3minutes. Keep board conditions distinct.

    G24M manual, page 28

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.