Lennox Split & Multi-Split

Lennox Error Code Red Trip LED ON

Split & Multi-Split

Red Trip LED ON means different things on different Split & Multi-Split models. Enter your model number to see only your reading, or find your model below.

What It Means

  • XC15: System and compressor check out OK
  • XP15: System and compressor check out OK Thermostat demand signal Y1 is present, but compressor not running NOTE - During 5-minute delay in LSOM the red trip LED will be on.
  • XC15: Thermostat demand signal Y1 is present, but compressor not running

Causes & actions from Lennox

System and compressor check out OK

Models: XC15

How it shows
  • lsom trip led: Red Trip LED ON (trip: on)

1Verify Y terminal is connected to 24VAC at contactor coil. 2Verify voltage at contactor coil falls below 0.5VAC when off. 3Verify 24VAC is present across Y and C when thermostat demand signal is present; if not present, R and C wires are reversed. 1Compressor protector is open. 2Outdoor unit power disconnect is open. 3Compressor circuit breaker or fuse(s) is open. 4Broken wire or connector is not making contact. 5Low pressure switch open if present in the system. 6Compressor contactor has failed to close.

Applicable models & manual sources

System and compressor check out OK Thermostat demand signal Y1 is present, but compressor not running NOTE - During 5-minute delay in LSOM the red trip LED will be on.

Models: XP15

How it shows
  • lsom trip led: Red Trip LED ON (trip: on)

1Verify Y terminal is connected to 24VAC at contactor coil. 2Verify voltage at contactor coil falls below 0.5VAC when off. 3Verify 24VAC is present across Y and C when thermostat demand signal is present; if not present, R and C wires are reversed. 1Compressor protector is open. 2Outdoor unit power disconnect is open. 3Compressor circuit breaker or fuse(s) is open. 4Broken wire or connector is not making contact. 5Low pressure switch open if present in the system. 6Compressor contactor has failed to close.

Applicable models & manual sources
  • XP15

    System and compressor check out OK Thermostat demand signal Y1 is present, but compressor not running NOTE − During 5-minute delay in LSOM the red trip LED will be on.

    XP15 manual, page 20

Thermostat demand signal Y1 is present, but compressor not running

Models: XC15

How it shows
  • lsom trip led: Red Trip LED ON (trip: on)

1Verify Y terminal is connected to 24VAC at contactor coil. 2Verify voltage at contactor coil falls below 0.5VAC when off. 3Verify 24VAC is present across Y and C when thermostat demand signal is present; if not present, R and C wires are reversed. 1Compressor protector is open. 2Outdoor unit power disconnect is open. 3Compressor circuit breaker or fuse(s) is open. 4Broken wire or connector is not making contact. 5Low pressure switch open if present in the system. 6Compressor contactor has failed to close.

Applicable models & manual sources
  • XC15

    Thermostat demand signal Y1 is present, but compres- sor not running

    XC15 manual, page 8

Disclaimer: This information is for general reference. Code wording and instructions vary by model. Always follow the service manual for your exact unit.